● 100% unbalanced output, each phase
● Max. charging/discharging current of 100A
● Support storing energy from diesel generator
● Max. 10 pcs parallel for on-grid and off-grid operation; Support multiple batteries parallel
● AC couple to retrofit existing solar system
● 6 time periods for battery charging/discharging
● High voltage battery, higher efficiency
| Model |
SUN-20K-SG01HP3 -US-BM3 |
SUN-25K-SG01HP3 -US-BM3 |
SUN-30K-SG01HP3 -US-BM4 |
| Battery Input Data | |||
| Battery Type | Lithium-ion | ||
| Battery Voltage Range (V) | 160-500 | ||
| Max. Charging Current (A) | 50+50 | ||
| Max. Discharging Current (A) | 50+50 | ||
| External Temperature Sensor | 2 | ||
| Number of Battery Input | Self-adaption to BMS | ||
| PV String Input Data | |||
| Max. DC Input Power (W) | 26000 | 32500 | 39000 |
| Max. DC Input Voltage (V) | 550 | ||
| Start-up Voltage (V) | 180 | ||
| MPPT Range (V) | 150-500 | ||
| Full Load DC Voltage Range (V) | 240-500 | 300-500 | 270-500 |
| Rated DC Input Voltage (V) | 380 | ||
| PV Input Current (A) | 36+36+36 | 36+36+36+36 | |
| Max. PV IS C (A) | 55+55+55 | 55+55+55+55 | |
| No.of MPP Trackers | 3 | 4 | |
| No.of Strings per MPP Tracker | 2+2+2 | 2+2+2+2 | |
| AC Output Data | |||
| Rated AC Output Active Power (W) | 20000 | 25000 | 30000 |
| Max. AC OutputActive Power (W) | 20000 | 25000 | 30000 |
| AC Output Rated Current (A) | 55.6 | 69.5 | 83.4 |
| Max. AC Output Current (A) | 55.6 | 69.5 | 83.4 |
| Max. Three-phase Unbalanced Output Current (A) | 80 | 85 | 90 |
| Max. Continuous AC Passthrough (A) | 200 | ||
| Peak Power (off grid) | 1.5 time of rated power, 10 S | ||
|
Generator Input/Smart Load /AC Couple Current (A) |
55.6 / 200 / 55.6 | 69.5 / 200 / 69.5 | 83.4 / 200 / 83.4 |
| Power Factor Adjustment Range | 0.8 leading to 0.8 lagging | ||
| Output Frequency and Voltage | 60Hz; 3L/N/PE 120/208Vac | ||
| Grid Type | Three Phase | ||
| Total Harmonics Current Distortion (THDi) | <3% (of nominal power) | ||
| DC Current Injection | <0.5% In | ||
| Efficiency | |||
| Max. Efficiency | 97.60% | ||
| Euro Efficiency | 97.00% | ||
| MPPT Efficiency | 99.90% | ||
| Protection | |||
| Integrated |
Anti-islanding Protection, PV String Input Reverse Polarity Protection, Insulation Resistor Detection, Residual Current Monitoring Unit, Output Over Current Protection, Output Shorted Protection, Surge Protection |
||
| Over Voltage Category | DC Type II/AC Type III | ||
| Certifications and Standards | |||
| Grid Regulation | IEEE 1547.1, SRD V2.0 | ||
| Safety / EMC Standard | FCC, UL 1741 | ||
| General Data | |||
| Operating Temperature Range (℃) | -40 to +60℃, >45℃ Derating | ||
| Cooling | Smart Cooling | ||
| Noise (dB) | ≤65 dB | ||
| Communication with BMS | CAN | ||
| Weight (kg) | 75 | ||
| Cabinet Size (WxHxD mm) | 527×894×294 (Excluding Connectors and Brackets) | ||
| Protection Degree | TYPE 3R | ||
| Installation Style | Wall-mounted | ||
| Warranty | 5 Years (10 Years Optional) | ||